Electrical control cabinet components installation wiring wiring specifications - Solutions - Huaqiang Electronic Network

Probe domestic switch needle KG-300K needle head diameter is 3.0mm normally open switch needle
100V, 250mA, surface mount, high speed switching diode

1 component installation
1.1 Prerequisite: All components shall be installed in accordance with the installation conditions specified by the manufacturer.
The arc-extinguishing distance required by the applicable conditions, the space required to remove the arc-extinguishing grid, etc. For the installation of the manual switch, it must be ensured that the arc of the switch is not dangerous to the operator.
1.2 First look at the drawings and technical requirements before assembly
1.3 Check if the product model, component model, specification, quantity, etc. match the drawing.
1.4 Check the components for damage
1.5 must be installed as shown (if there is a picture)
1.6 Component assembly sequence should be from the front of the board, from left to right, from top to bottom
1.7 The same model should ensure assembly consistency
1.8 The height of the center line of the component on the panel and door panel should meet the specified component name installation height (m)
Indication meter, indicator light 0.6-2.0
Energy meter 0.6-1.8
Control switch, button 0.6-2.0
Emergency operation parts 0.8-1.6
The assembled product should meet the following conditions:
Easy to operate. When the components are in operation, they should not be affected by the space, and there should be no possibility of touching the charged body.
Easy to repair. It is convenient to replace components and repair wiring.
The clearance and creepage distance of various electrical components and devices shall comply with the provisions of 4.4.
Ensure the installation distance of the first and second lines.
1.9 The fasteners and metal parts used for assembly shall be provided with a protective layer. The burrs and sharp edges of the screw holes, edges and surfaces shall be ground and then coated with conductive paste.
1.10 For the fastening of the bolt, the appropriate tool should be selected, the protective layer of the fastener should not be damaged, and the corresponding torque should be noted.
1.11 Components on the main circuit, general reactors, transformers need to be grounded, circuit breakers do not need to be grounded, the reactor is grounded in the figure below.
Digital camera
1.12 For the installation of heating elements (such as tubular resistors, heat sinks, etc.), the heat dissipation should be considered. The installation distance should be in accordance with the component specifications. Tube resistors rated at 75W and above shall be mounted horizontally and shall not be installed vertically on the vertical floor. The following figure is the wrong connection
Digital camera
1.13 All electrical components and accessories shall be fixedly mounted on brackets or base plates and shall not be suspended from electrical appliances and wiring.
1.14 There is a sign near each component of the wiring surface, and the mark should match the drawing. The sign shall not be fixed to the component body except that the component itself is provided with a sign for filling.
a) Identification of the terminal
Digital camera
1.15 The markings should be complete, clear and strong. The label pasting position should be clear and eye-catching
b) double identification
Digital camera
1.16 The components mounted on the panel and door panel shall be attached to the panel and the back panel of the door panel. If there is no position as shown below, it can be attached to the left, but the bonding position is as consistent as possible.
c) the device on the door
Digital camera
1.17 Protective Earth Continuity Protection Grounding continuity is ensured by effective wiring.
If any two metal parts in the cabinet are connected by screws, if there is insulation layer, the grounding washer of the corresponding specification should be used and the tooth surface of the washer should be in contact with the surface of the component (at the red circle) or the insulation layer should be damaged.
Digital camera
Digital camera
1.18 When installing components that are susceptible to vibration, install a rubber pad between the components and the mounting plate to absorb vibration.
1.19 For components with operating handles, they should be adjusted in place and must not be jammed.
Digital camera

HD Mini Projector

HD Mini Projector-1080P high-resolution display, magnify the details and present a clear picture, without any distortion in direct projection. The LED light source system integrates color control to improve the brightness, quality and stability of the picture, and present the real world in front of your eyes.

led home projector 1080p,1080p home cinema projector,wifi 1080p home theater projector